How to Size a Battery Energy Storage System (ESS)

Battery capacity in kWh, inverter power in kW and usable depth of discharge decide whether an ESS meets your needs. Here is how to size one step by step.

Home garage with a wall-mounted solar inverter and two EEMENTOR ENERGY 48V LiFePO4 battery packs, solar house in the background
Home garage with a wall-mounted solar inverter and two EEMENTOR ENERGY 48V LiFePO4 battery packs, solar house in the background

A battery energy storage system (ESS) stores electricity from solar panels or the grid and releases it when you need it: in the evening, during peak tariff hours or in a power cut. Sizing it correctly means getting two numbers right: energy (kWh) and power (kW).

Step 1: what do you want the ESS to do?

  • Solar self-consumption: store daytime solar for evening use.
  • Backup power: keep essential loads running during outages.
  • Peak shaving: reduce grid demand during expensive hours, common for businesses.
  • Off-grid: supply all energy where there is no grid connection.

Step 2: energy (kWh)

Look at the energy you need to cover from the battery. For self-consumption, use your typical evening and night consumption. For backup, add up the essential loads: power (kW) × hours of backup. For example, 1.5 kW of essential loads for 4 hours needs 6 kWh.

Step 3: usable capacity and margins

Not all nominal capacity is usable every day. Allow for the depth of discharge set in the system, inverter losses and some reserve. A common approach is to divide the energy need by about 0.8 to 0.9. 6 kWh of need becomes roughly 7 kWh of installed capacity. LiFePO4 batteries are well suited to daily deep cycling; see LiFePO4 vs lithium-ion.

Step 4: power (kW)

The inverter and battery must deliver the peak power of the loads that run at the same time, plus start-up surges of motors and pumps. A system with plenty of kWh but too little kW will shut down when several large loads switch on.

Step 5: voltage and compatibility

Most home and small commercial systems use 48 V class batteries (15S at 48 V or 16S at 51.2 V nominal for LiFePO4). The battery must be compatible with the inverter, ideally with closed-loop communication over CAN or RS485 so the inverter knows the battery's state of charge and limits.

Step 6: plan for growth

Consumption often grows with heat pumps, EV charging or business expansion. Modular systems let you add capacity later by connecting more modules in parallel. Our guide to ESS formats compares the options.

Worked example

A small business wants 10 kWh of evening energy from solar and 3 kW of continuous load: 10 / 0.85 ≈ 12 kWh installed. Two 51.2 V 100 Ah wall-mounted batteries give about 10.2 kWh; three give about 15.4 kWh with room for growth, paired with an inverter of at least 3–5 kW.

Bar chart of the ESS sizing example: 10 kWh of evening energy needed; 10 ÷ 0.85 ≈ 12 kWh installed; two 51.2 V 100 Ah batteries give about 10.2 kWh, below the target; three give about 15.4 kWh, above the target with room for growth.
The worked example: two batteries fall short of the 12 kWh target, three meet it with room to grow.

Our ESS ranges

Work with EEMENTOR ENERGY™

Want help sizing a storage system? Explore our custom battery pack service, energy storage systems and LiFePO4 deep cycle batteries, try configurations in the Battery Design Studio, or request an engineering review and our engineering team will reply with questions or a proposal. Custom packs and engineering projects are for business customers; our battery cells are available to everyone, including hobbyists and DIY builders.