Every lithium battery pack is built from individual cells connected in series (S) and parallel (P). The configuration code, such as 7S12P or 14S8P, tells you almost everything about the pack's electrical behaviour. Here is how to read it.
Series: adds voltage
Connecting cells in series (positive to negative) adds their voltages while the capacity stays the same as one cell.
- Lithium-ion cells: 3.6 V nominal, 4.2 V fully charged, typically around 2.5 to 3.0 V empty.
- LiFePO4 cells: 3.2 V nominal, 3.65 V fully charged.
So a 7S lithium-ion pack is 7 × 3.6 V = 25.2 V nominal and 7 × 4.2 V = 29.4 V fully charged. A 4S LiFePO4 pack is 12.8 V nominal, which is why it is a popular replacement for 12 V lead-acid batteries (see our deep cycle batteries).
Parallel: adds capacity and current
Connecting cells in parallel (positive to positive) keeps the voltage of one cell but adds the capacity and the current capability. Twelve 2.5 Ah cells in parallel give 30 Ah. If each cell can deliver 20 A continuously, the group can deliver about 240 A, before derating for the BMS, wiring and temperature.
Putting it together: 7S12P
A 7S12P pack has 7 groups in series, and each group has 12 cells in parallel: 84 cells in total. With Samsung 25R cells (3.6 V, 2.5 Ah, 20 A):
- Voltage: 7 × 3.6 V = 25.2 V nominal
- Capacity: 12 × 2.5 Ah = 30 Ah
- Energy: 25.2 V × 30 Ah = 756 Wh
- Cell current limit: 12 × 20 A = 240 A

Another example: 14S8P
With LG MJ1 cells (3.6 V, 3.5 Ah, 10 A), a 14S8P pack gives 50.4 V nominal, 28 Ah, about 1,411 Wh and a cell current limit of 80 A. That is a typical configuration for e-mobility and robotics.
Why the balance between S and P matters
- More series means higher voltage and lower current for the same power, so thinner wires and less heat, but a BMS with more channels.
- More parallel means more capacity, more current capability and lower stress per cell, which improves lifetime.
- Cells in a pack should be matched (same model, batch, voltage and internal resistance) so they share the load evenly.
Common mistakes
- Confusing nominal and maximum voltage when choosing a controller or charger.
- Using the cell's peak current instead of its continuous rating.
- Forgetting that the BMS, not the cells, often limits the pack's current.
Want to see these numbers change live? Set series and parallel counts in our Battery Design Studio, or read the full battery pack design guide.