Quick answer: size a commercial battery from power first, then energy. Work out how many kilowatts you need to remove from the peak (or carry in an outage) and for how long, and divide the energy by about 0.85. A 100–200 kWh system in our cabinet range is, for example, four to six 30.72 kWh high-voltage cabinets: 122.9 to 184.3 kWh, with about 30.7 kW of discharge per cabinet. Low-voltage cabinets store the same energy but deliver far less power each, so they suit backup more than peak shaving.
Businesses use battery storage to cut peak demand charges, store solar for later in the day and keep critical loads running. This guide shows how to size a system in the 100–200 kWh range. For the general method and home systems, read how to size a battery energy storage system and home battery storage: 10 or 15 kWh.
Step 1: what the system must do
- Peak shaving: discharge during the site's demand peaks to keep grid demand below a target. Sized by the kilowatts to remove and the length of the peak.
- Solar self-consumption: store midday solar surplus for the afternoon and evening. Sized by the daily surplus and the evening load.
- Backup and UPS: carry critical loads (servers, telecom, refrigeration, controls) through an outage. Sized by the critical load and the backup time.
Many sites combine them; size for the most demanding one and set reserves in the energy management system.
Step 2: a peak-shaving example
A site peaks at 180 kW for about two hours each afternoon and wants to keep grid demand at 130 kW. These are example inputs; use 15-minute interval data from your meter or energy supplier.
- Power to shave: 180 − 130 = 50 kW.
- Energy per peak: 50 kW × 2 h = 100 kWh.
- Installed energy with about 85% usable: 100 ÷ 0.85 ≈ 118 kWh.
- Four 307100-96S-CBH high-voltage cabinets (307.2 V, 30.72 kWh each): 122.9 kWh. Their combined maximum discharge, about 123 kW, covers the 50 kW with a wide margin.
Check the inverter or power conversion system (PCS) as well: it sets the power the site actually sees. Here a PCS of at least 50 kW is needed.
Low-voltage or high-voltage cabinets
Our cabinets come in low-voltage (48 V class) and high-voltage versions. Same LiFePO4 chemistry and similar sizes, but very different power per cabinet:
| Model | Voltage | Energy | Max discharge (calculated power) | Size and weight |
|---|---|---|---|---|
| 48300-16S-CBL (LV) | 51.2 V | 15.36 kWh | 100 A (about 5.1 kW) | 745 × 415 × 590 mm, about 195 kg |
| 153100-48S-CBH (HV) | 153.6 V | 15.36 kWh | 100 A (about 15.4 kW) | 745 × 415 × 590 mm, about 195 kg |
| 204100-64S-CBH (HV) | 204.8 V | 20.48 kWh | 100 A (about 20.5 kW) | 930 × 415 × 590 mm, about 260 kg |
| 256100-80S-CBH (HV) | 256 V | 25.6 kWh | 100 A (about 25.6 kW) | 1120 × 415 × 590 mm, about 310 kg |
| 307100-96S-CBH (HV) | 307.2 V | 30.72 kWh | 100 A (about 30.7 kW) | 1300 × 415 × 590 mm, about 360 kg |
Model data from our energy storage systems page; power is the listed maximum discharge current × nominal voltage. The 15.36 kWh LV and HV cabinets have the same size and weight, but the HV cabinet delivers three times the power. To shave 50 kW at 51.2 V, a system needs about 980 A, ten LV cabinets' worth of discharge current; at 307.2 V it needs about 163 A.
Low-voltage systems still make sense for backup and telecom loads that draw modest power for many hours, and where the existing equipment is built for 48 V.

Building 100–200 kWh
| Configuration | Energy (calculated) | Max discharge (calculated) | Weight of batteries |
|---|---|---|---|
| 7 × 153100-48S-CBH (153.6 V) | 107.5 kWh | about 108 kW | about 1,365 kg |
| 4 × 307100-96S-CBH (307.2 V) | 122.9 kWh | about 123 kW | about 1,440 kg |
| 5 × 307100-96S-CBH (307.2 V) | 153.6 kWh | about 154 kW | about 1,800 kg |
| 6 × 307100-96S-CBH (307.2 V) | 184.3 kWh | about 184 kW | about 2,160 kg |
| 15 × 48200-16S-CB modules (51.2 V, 10.3 kWh each) | about 155 kWh | about 154 kW (200 A each) | about 1,440 kg |
Totals assume the units are combined in parallel at full rating; the cabinet range is listed as scalable to 230 kWh, and the modules stack up to 15. How cabinets are combined, and with which PCS, is engineered and confirmed for each project. The weights show why floor loading and access need planning early: six 30.72 kWh cabinets weigh more than two tonnes.
Cycle life: size for the depth you use
The cabinet range lists at least 3,000 cycles at 80% depth of discharge and at least 5,000 cycles at 60% (25 °C, 0.5C) in the manufacturer's datasheet, with a design life of at least 10 years. At one full cycle a day, 3,000 cycles is just over 8 years; 5,000 cycles is nearly 14. A slightly larger system that cycles at 60% instead of 80% therefore reaches its design life with fewer cycles used. In the example above, 122.9 kWh against a 100 kWh daily peak is about 81% depth; five cabinets bring it to about 65%.
Site, safety and communication
- Temperature: the cabinets charge between 0 and 45 °C and discharge between −10 and 50 °C. Plan a ventilated or climate-controlled room, or an enclosure rated for the site.
- Communication: CANBus, RS485 and RS232, with a smart BMS, cell matching and cloud monitoring. The PCS and energy management system read the battery limits and state of charge over the agreed protocol.
- Certification: the cabinet range lists IEC 62619 and UN38.3 for the standard models in the manufacturer's datasheet; ask us for the documents for your configuration. See battery certifications explained.
- Fire safety and permits: local rules for battery rooms, spacing and fire detection differ widely; involve your installer and fire-safety adviser at the design stage.
- EU battery passport: industrial batteries above 2 kWh need a digital battery passport from 18 February 2027. See the EU battery passport guide.
Getting a commercial storage system
Send us your interval data or peak profile, the purpose (peak shaving, solar, backup), the PCS or inverter if you have one, and the space available. Our engineers will propose the cabinets, the configuration and the communication setup, and confirm compatibility. Request a quote, browse the cabinet systems, or read our guide to ESS formats.
Frequently asked questions
How much battery storage does a business need?
Start from the purpose. For peak shaving, multiply the power you want to remove from the peak by how long the peak lasts; for backup, multiply the critical load by the backup time. Divide by about 0.85 for usable capacity and losses, then check that the batteries and inverter deliver the power.
Low-voltage or high-voltage cabinets for commercial storage?
For the same power, a high-voltage cabinet carries far less current. Our 307.2 V cabinet delivers about 30.7 kW at its 100 A maximum discharge, while a 51.2 V cabinet of similar size delivers about 5.1 kW. Above a few tens of kilowatts, high-voltage systems usually need fewer parallel units and smaller cables.
How long do commercial LiFePO4 cabinets last?
Our cabinet range lists at least 3,000 cycles at 80% depth of discharge and at least 5,000 cycles at 60% (25 °C, 0.5C), with a design life of at least 10 years, in the manufacturer's datasheet. At one cycle a day, 3,000 cycles is just over 8 years.
Which inverter works with commercial battery cabinets?
A commercial hybrid inverter or power conversion system (PCS) rated for the battery voltage and power, communicating with the battery BMS over a supported protocol. Our cabinets support CANBus, RS485 and RS232; we confirm compatibility with your inverter.
Do commercial batteries need an EU battery passport?
Industrial batteries above 2 kWh placed on the EU market need a digital battery passport from 18 February 2027, so every cabinet in a commercial system is in scope.